Author:

Li, L. T. (Li, L. T..) | Wang, W. (Wang, W..) (Scholars:王伟) | Sun, Y. Y. (Sun, Y. Y..) | Feng, Y. C. (Feng, Y. C..) | Lu, W. P. (Lu, W. P..) | Zhu, J. H. (Zhu, J. H..) | Ge, Y. J. (Ge, Y. J..)

Indexed by:

EI Scopus SCIE

Abstract:

To investigate the impact of defrosting-water retention on the surface of heat exchangers of the air source heat pump (ASHP) performance during frosting-defrosting cycles, an experimental study has been conducted. Testing was carried out in a controlled-environment chamber with ASHP operational data collected over 16 periodic frosting-defrosting cycles spanning a 360-min period. It was found that the defrosting-water retention undergoes three stages: single-phase water, a mixture of water and ice, followed by a predominance of ice. In this study, the third stage appears after the unit has been in operation for 256 mm. A "permafrost area" forms on the lower quadrant of the heat exchanger, which occupies over 20% of the total heat exchanger surface. This area remained continuously occupied regardless of whether the unit was in a frosting or defrosting cycle. The appearance of this "permafrost area" not only impacts the performance of the ASHP, it also indicates the beginning of repetitive "shutdown accidents" for the ASHP units. It is the first time that these phenomena, originally caused by the defrosting-water retention have been revealed. And a quantitative analysis is presented for the resulting performance degradation of the ASHP related to the "permafrost area" conditions and the related "repetitive shutdown accidents". (C) 2014 Elsevier Ltd. All rights reserved.

Keyword:

Defrosting Permafrost area Frosting Water retention Air source heat pump

Author Community:

  • [ 1 ] [Li, L. T.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
  • [ 2 ] [Wang, W.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
  • [ 3 ] [Sun, Y. Y.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
  • [ 4 ] [Feng, Y. C.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
  • [ 5 ] [Lu, W. P.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
  • [ 6 ] [Zhu, J. H.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
  • [ 7 ] [Ge, Y. J.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China

Reprint Author's Address:

  • 王伟

    [Wang, W.]Beijing Univ Technol, Dept Bldg Environm & Facil Engn, Coll Architecture & Civil Engn, 100 Pingleyuan Rd, Beijing 100124, Peoples R China

Show more details

Related Keywords:

Source :

APPLIED ENERGY

ISSN: 0306-2619

Year: 2014

Volume: 135

Page: 98-107

1 1 . 2 0 0

JCR@2022

ESI Discipline: ENGINEERING;

ESI HC Threshold:176

JCR Journal Grade:1

CAS Journal Grade:1

Cited Count:

WoS CC Cited Count: 48

SCOPUS Cited Count: 51

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 11

Online/Total:414/10499484
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185