Abstract:

During experiments on investigating the application feasibility of variable-frequency air source heat pump with vapor injection (ASHPVI) in severe cold region, it was found its frosting performance varied significantly from that in former investigations, e.g. in a severe frosting condition (0 degrees C, 80%), the experimental unit was frost-free. To investigate the frosting characteristics of variable-frequency ASHPVI for space heating in severe cold region, a test rig was built and used to supply heating for a lab in two heating seasons. A new frosting map was developed through summarizing its running performance under frosting condition. Results showed the frosting map of variable-frequency ASHPVI was affected by heating load. Owing to the consideration of heating load, the critical relative humidity decreased from 80.60% to 62.75% when outdoor temperature (OT) dropped from 1.0 degrees C to -26.5 degrees C, opposite to the change trend in former investigations. Besides, compared with values obtained in cold region, the upper and lower limits of OT of frosting region in severe cold region were both lower, and its critical relative humidity was higher. Moreover, the highest frosting speed appeared at OT of approximately -10 degrees C in severe cold region, but not at 0 degrees C as previously thought. (C) 2020 Elsevier Ltd. All rights reserved.

Keyword:

Severe cold region Air source heat pump Heating load Variable-frequency Frosting map

Author Community:

  • [ 1 ] [Wei, Wenzhe]Harbin Inst Technol, Sch Architecture, Key Lab Cold Reg Urban & Rural Human Settlement E, Minist Ind & Informat Technol, Harbin, Peoples R China
  • [ 2 ] [Ni, Long]Harbin Inst Technol, Sch Architecture, Key Lab Cold Reg Urban & Rural Human Settlement E, Minist Ind & Informat Technol, Harbin, Peoples R China
  • [ 3 ] [Li, Shuyi]Harbin Inst Technol, Sch Architecture, Key Lab Cold Reg Urban & Rural Human Settlement E, Minist Ind & Informat Technol, Harbin, Peoples R China
  • [ 4 ] [Yao, Yang]Harbin Inst Technol, Sch Architecture, Key Lab Cold Reg Urban & Rural Human Settlement E, Minist Ind & Informat Technol, Harbin, Peoples R China
  • [ 5 ] [Wang, Wei]Beijing Univ Technol, Coll Architecture & Civil Engn, Dept Bldg Environm & Facil Engn, 100 Pingleyuan, Beijing 100124, Peoples R China
  • [ 6 ] [Xu, Laifu]Nanjing TICA Climate Solut CO Ltd, Nanjing, Peoples R China
  • [ 7 ] [Yang, Yahua]Nanjing TICA Climate Solut CO Ltd, Nanjing, Peoples R China

Reprint Author's Address:

  • [Ni, Long]Harbin Inst Technol, Sch Architecture, Key Lab Cold Reg Urban & Rural Human Settlement E, Minist Ind & Informat Technol, Harbin, Peoples R China

Show more details

Related Keywords:

Source :

RENEWABLE ENERGY

ISSN: 0960-1481

Year: 2020

Volume: 161

Page: 184-199

8 . 7 0 0

JCR@2022

ESI Discipline: ENGINEERING;

ESI HC Threshold:115

Cited Count:

WoS CC Cited Count: 34

SCOPUS Cited Count: 38

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 2

Online/Total:1130/10478249
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185
Copyright:BJUT Library Technical Support:Beijing Aegean Software Co., Ltd.