Abstract:
<正> 1 区域供冷系统区域供冷可以定义为:由一个或多个制冷站生产空调用冷水,由连接制冷站和各建筑的管网向该区域各类建筑输送空调冷水的系统。中关村一期冷站设计日总冷量为523155KWH,蓄冷量总计100451KWH。空调峰值负荷41710KW,夜间谷值最小负荷2600KW。冷站的冰蓄冷流程采用主机上游的串联循环回路方式,系统可按4种工作模式运行,(1)主机独立供冷(2)主机单独制冰(3)主机与融冰释冷联合运行(4)融冰释冷联合运行。