Indexed by:
Abstract:
A three-dimensional full scale geometry model was established by Computational Fluid Dynamics (CFD) software based on the typical Subway Transfer Station (STS) of Beijing. Taking Navier-Stokes equations and renormalization group (RNG) k-epsilon two-equation turbulence model as mathematical model, applying numerical method simulates air distribution of ventilation and air-conditioning system in subway transfer station. The result shows that the piston wind effect is obvious, which resulted in some temperature rised on waiting train zone. Meanwhile, it has a significant impact on air distribution of up and down platform and transfer channels. Despite the interaction of air distribution between the two stations of subway transfer station was occurred, the distribution of temperature and velocity field are relatively uniform and comparative satisfactory, which meet the requirements of transitory comfort for passengers. So, the ventilation and air-conditioning system are rational and anticipant. In conclusion, CFD technology can provide theoretic reference for thermal environment design and optimize ventilation and air conditioning design of subway transfer station.
Keyword:
Reprint Author's Address:
Email:
Source :
FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS
Year: 2009