Author:

Ma, Guo-Yuan (Ma, Guo-Yuan.) (Scholars:马国远) | Wang, Shu-Chun (Wang, Shu-Chun.) | Zhou, Feng (Zhou, Feng.)

Indexed by:

EI Scopus PKU CSCD

Abstract:

To reduce the power consumption of air conditioners used for cooling telecommunication base stations, the thermosyphon heat exchanger unit is presented for the base station heat dissipation assisting with the air conditioner. An air to air thermosyphon heat exchanger unit is designed and tested. Results indicate that the heat exchanger unit works well with good heat dissipation performance under the testing conditions. The temperature effectiveness of the unit can reach 50%, and the energy efficiency ration (EER) reaches 10.9.

Keyword:

Well testing Capillary flow Thermosyphons Siphons Base stations Energy efficiency Air conditioning Domestic appliances Energy conservation

Author Community:

  • [ 1 ] [Ma, Guo-Yuan]College of Environmental and Energy Engineering, Beijing University of Technology, Beijing 100124, China
  • [ 2 ] [Wang, Shu-Chun]College of Environmental and Energy Engineering, Beijing University of Technology, Beijing 100124, China
  • [ 3 ] [Zhou, Feng]College of Environmental and Energy Engineering, Beijing University of Technology, Beijing 100124, China

Reprint Author's Address:

Show more details

Related Keywords:

Related Article:

Source :

Journal of Beijing University of Technology

ISSN: 0254-0037

Year: 2012

Issue: 10

Volume: 38

Page: 1554-1559

Cited Count:

WoS CC Cited Count: 0

SCOPUS Cited Count:

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 8

Online/Total:414/10520204
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185