The thermal performance of pin-fin heat sinks with confined and submerged liquid water jet array impingement was investigated experimentally. The experimental results indicate that: the performance of heat sinks is closely related to the height of the pin-fin, but not the higher the better; Nusselt number is represented by pyramidal distribution in 0.625≤W/G≤1.000; for the confined and submerged jet arrays a strong dependence on both jet-to-target and jet-to-jet spacing can be observed, and Nusselt number falls continuously between 2.5≤H/d≤10.0; an increment in jet-to-jet spacing between 3.00~4.50 can be found to decrease Nusselt number when Re