Indexed by:
Abstract:
The study on the operating characteristics of heat pump in ventilation heat recovery system can point out the way of improvement for heat pump in this application. An experimental platform was set to conduct a comprehensive study on the heat pump ventilation heat recovery system in winter conditions. The results show that under the experimental conditions, the system pressure ratio, power input and refrigerant mass flow rate decrease with the decrease of outdoor temperature; the recovered heat, temperature effectiveness and COP (coefficient of performance) increase with the decrease of outdoor temperature. Increasing the mass flow rate of the system can be an effective way to improve the performance of heat pump type ventilation heat recovery system. © 2019 International Institute of Refrigeration. All rights reserved.
Keyword:
Reprint Author's Address:
Email:
Source :
ISSN: 0151-1637
Year: 2019
Volume: 2019-August
Page: 4302-4309
Language: English
Cited Count:
SCOPUS Cited Count:
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 7