Data centers must be cooled appropriately through indoor temperature control in order to improve information technology (IT) equipment reliability. Free cooling is a promising technology for energy conservation in data centers. A miniature pump-driven loop heat pipe (PLHP) unit for free cooling is developed for a small data center. The unit consumes low power and has a high energy efficiency ratio (EER) compared with air conditioners. The operating performance of the PLHP unit installed in the case data center in Beijing was tested and studied. The EERs under different outdoor temperatures were analyzed, and the fitting variation rules were obtained. Compared with air conditioners, the annual energy savings of the PLHP unit for both hours and days were tested and analyzed based on the fitting formula. Results show that indoor temperature is maintained at 18-25 degrees C, and that the test energy saving ratio is over 20.18%. Hence, the PLHP unit can replace air conditioners for cooling the case data center. (c) 2017 Elsevier Ltd. All rights reserved.

Keyword:

Case analysis Free cooling Data center Pump-driven loop heat pipe Energy saving

Author Community:

  • [ 1 ] [Zhou, Feng]Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100124, Peoples R China
  • [ 2 ] [Wei, Chuancheng]Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100124, Peoples R China
  • [ 3 ] [Ma, Guoyuan]Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100124, Peoples R China

Reprint Author's Address:

  • 马国远

    [Ma, Guoyuan]Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100124, Peoples R China

Show more details

Related Keywords:

Source :

APPLIED THERMAL ENGINEERING

ISSN: 1359-4311

Year: 2017

Volume: 124

Page: 1169-1175

6 . 4 0 0

JCR@2022

ESI Discipline: ENGINEERING;

ESI HC Threshold:165

CAS Journal Grade:1

Cited Count:

WoS CC Cited Count: 63

SCOPUS Cited Count: 71

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 7

Online/Total:291/10567531
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185
Copyright:BJUT Library Technical Support:Beijing Aegean Software Co., Ltd.