In order to analyze the effect of the smoke exhaust system, a series of experiments were conducted in a 1:20 scale model of a cross-type interchange subway station. Fire dynamics simulator code was used to evaluate different mechanical smoke control strategies conducted in a full-scale interchange subway station. The numerical results were compared with experimental data. Results show that the experimental data of the air temperature distribution in the station platform were in good agreement with the simulation results and the research indicated that the different smoke control system had different influence on smoke confinement induced by the fire occurred in the 3rd basement, which was the platform of the No.10 line in Beijing. In the same smoke control strategy, the velocity of airflow at stairs with a full-seal screen platform door system in the transfer station is higher than that of platform the half-height screen platform door system.