A fire happens in head of train stopped in a subway station JSTSS is studied by using a three dimensional CFD modeling. The fire is 5.0 MW and it is modeled as a heat source located on the left side of subway station during simulation. Three smoke control strategies including exhaust only, push-pull and push-push are discussed. Air temperature distributions on the plane which is 2.3 m above the platform floor for these three strategies are overviewed. According to the criteria of NFPA 130 standard, the push-pull strategy is determined as the optimum scheme for smoke control under this fire scenario. The results also show that that detailed prediction of CFD models provide the necessary analysis capability for suitably designing and operating ventilation systems in order to support passenger evacuation.

Keyword:

subway station fire CFD smoke control ventilation

Author Community:

  • [ 1 ] Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100022, Peoples R China

Reprint Author's Address:

  • 李炎锋

    [Li Yanfeng]Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100022, Peoples R China

Email:

Show more details

Related Keywords:

Related Article:

Source :

PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL 6, PTS A AND B

Year: 2006

Volume: 6

Page: 865-868

Language: English

Cited Count:

WoS CC Cited Count: 0

SCOPUS Cited Count:

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 5

Online/Total:440/10558111
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185
Copyright:BJUT Library Technical Support:Beijing Aegean Software Co., Ltd.