Indexed by:
Abstract:
In order to improve the temperature efficiency of the pump-driven loop heat pipe system and explore the technical feasibility of replacement of the single-loop pump-driven loop heat pipe system by the multi-loop pump-driven loop heat pipe system for energy recovery from exhaust air in public buildings, a single-loop and a triple-loop pump-driven loop heat pipe system prototype were developed. An experimental setup was built to contrast the heat transfer characteristics between the single-loop system and the triple-loop system under summer and winter working conditions based on the principle of heat transfer temperature difference uniformity. Results indicated that performance of the triple-loop system was better. Compared with the single-loop system, the temperature efficiency of the triple-loop system was improved by 22.6% under winter working condition when the temperature difference between indoor and outdoor air was 31.9 because the temperature difference uniformity was much better, while the temperature efficiency changed little under summer working condition. © All Right Reserved.
Keyword:
Reprint Author's Address:
Email:
Source :
CIESC Journal
ISSN: 0438-1157
Year: 2017
Issue: 1
Volume: 68
Page: 104-111
Cited Count:
WoS CC Cited Count: 0
SCOPUS Cited Count:
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 1
Affiliated Colleges: