Abstract:

With the vertical stacking of circuit layers, the power density of 3D-IC increases exponentially. Interlayer liquid cooling is a promising and scalable solution for high heat flux removal in 3D-IC (three-dimensional integration circuit). The flow and heat transfer performances of water through uniform and double-side heat flux 3D-IC of interlayer in-line micro-pin fins structure with heat transfer areas of 1 cm2 and Reynolds number ranging from 150 to 900 were studied numerically. 3D-IC with in-line micro-pin fins for pitches of 200 μm, diameter of 100 μm and heights of 200 μm was analyzed. Results show that interlayer liquid cooling of 3D-IC with in-line micro-pin fins has better heat exchange effect than that with rectangular micro-channels. For the Reynolds number of 770, the power reaches to 250 W, which is equivalent to 8.3 kW/cm3 volumetric heat. Compared with rectangular micro-channels, the average temperature and the maximal junction temperature of the heater surface with in-line micro-pin fins are only 46.34, 13.96 K, down by 13.26, 21.34 K, respectively. © 2017, Editorial Department of Journal of Aerospace Power. All right reserved.

Keyword:

Liquids Heat flux Three dimensional integrated circuits Heat convection Fins (heat exchange) Reynolds number Heat transfer performance Timing circuits Cooling

Author Community:

  • [ 1 ] [Ma, Dandan]Key Laboratory of Enhanced Heat Transfer and Energy Conservation, School of Environmental and Energy Engineering, Beijing University of Technology, Beijing; 100124, China
  • [ 2 ] [Xia, Guodong]Key Laboratory of Enhanced Heat Transfer and Energy Conservation, School of Environmental and Energy Engineering, Beijing University of Technology, Beijing; 100124, China
  • [ 3 ] [Chen, Zhuo]Key Laboratory of Enhanced Heat Transfer and Energy Conservation, School of Environmental and Energy Engineering, Beijing University of Technology, Beijing; 100124, China
  • [ 4 ] [Wang, Zhuo]Key Laboratory of Enhanced Heat Transfer and Energy Conservation, School of Environmental and Energy Engineering, Beijing University of Technology, Beijing; 100124, China

Reprint Author's Address:

  • 夏国栋

    [xia, guodong]key laboratory of enhanced heat transfer and energy conservation, school of environmental and energy engineering, beijing university of technology, beijing; 100124, china

Show more details

Related Keywords:

Source :

Journal of Aerospace Power

ISSN: 1000-8055

Year: 2017

Issue: 7

Volume: 32

Page: 1569-1576

Cited Count:

WoS CC Cited Count:

SCOPUS Cited Count: 1