Based on a quasi 3-D steady model inside and a 2-D unsteady model outside of the borehole of ground heat exchanger(GHE), the relationship between the heat exchange rate per depth of borehole and main parameters (center-to-center distance of two branch pipes, radius and depth of the borehole) has been analyzed. The rational values of those design parameters with considering the heat exchange rate per depth of borehole are obtained. The dynamic simulations of underground temperature field (UTF) of single-pipe and pipe-group of U-tube GHE have been conducted by ANSYS. The change rules of UTF are obtained when ground source heat pump(GSHP) has experienced a complete cooling and heating cycle during one year. The simulation results of a single-pipe show that the action radius of borehole is 1.9 m, i.e., it is reasonable that the borehole center-to-center distance is 3.8 m. The simulation results of pipe-group indicate that temperature of the soil center encircled by four boreholes at the beginning of heating in winter is higher than the initial temperature of soil, but it is in opposite for cooling in summer, which is beneficial to the efficient operation of GSHP. This work can provide guidance for the rational design and operation of GSHP. (C) 2019 Elsevier Ltd. All rights reserved.
Keyword:
Reprint Author's Address:
Email:
Source :
ENERGY
ISSN: 0360-5442
Year: 2019
Volume: 174
Page: 138-147
9 . 0 0 0
JCR@2022
ESI Discipline: ENGINEERING;
ESI HC Threshold:136
JCR Journal Grade:1
Cited Count:
WoS CC Cited Count: 13
SCOPUS Cited Count: 13
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 2
Affiliated Colleges: