Abstract:

Air conditioning system (AC) contributes significantly to the energy consumption of underground metros. In China, most metro stations are designed with water-cooling centralized air conditioning (WC-AC) system, it has been found that several serious problems are brought by this conventional system, such as large space occupying, water leaking, cooling tower noise and low system efficiency. In order to solve these problems, a novel energy-efficient AC system incorporating an independent evaporative condenser (EC) has been proposed and installed at Eutong metro station in Beijing, China. A series of pilot measurements were conducted to analyze the cooling performance and energy consumption of this novel EC-AC system. During the testing period, the average refrigeration efficiency of COP, SCOP and ACOP in A and B side is up to 3.8/3.9, 3.4/3.4 and 2.5/2.3. At the same time, some operation problems such as unbalanced working condition have been identified during measurement. The research indicates that such EC-AC system could be a feasible solution to enhance the energy efficiency and reduce the operational costs and carbon emission in metro stations.

Keyword:

Air conditioning Energy conservation Performance evaluation Evaporative condenser Metro station

Author Community:

  • [ 1 ] [Pan, Song]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Eff, Beijing 100124, Peoples R China
  • [ 2 ] [Pei, Fei]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Eff, Beijing 100124, Peoples R China
  • [ 3 ] [Wang, Hongwei]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Eff, Beijing 100124, Peoples R China
  • [ 4 ] [Liu, Jiaping]Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Eff, Beijing 100124, Peoples R China
  • [ 5 ] [Wei, Yixuan]Univ Nottingham, Res Ctr Fluids & Thermal Engn D, Dept Architectural & Built Environm, Ningbo 315100, Zhejiang, Peoples R China
  • [ 6 ] [Zhang, Xingxing]Dalarna Univ, Sch Ind Technol & Business Studies, S-79188 Falun, Sweden
  • [ 7 ] [Li, Guoqing]Beijing Inst Residential Bldg Design & Res Co LTD, Beijing 100005, Peoples R China
  • [ 8 ] [Gu, Yaxiu]Changan Univ, Coll Architectural Engn, Res Lab HVAC, Xian 710061, Shaanxi, Peoples R China

Reprint Author's Address:

  • [Wei, Yixuan]Univ Nottingham, Res Ctr Fluids & Thermal Engn D, Dept Architectural & Built Environm, Ningbo 315100, Zhejiang, Peoples R China;;[Zhang, Xingxing]Dalarna Univ, Sch Ind Technol & Business Studies, S-79188 Falun, Sweden

Show more details

Related Keywords:

Related Article:

Source :

SUSTAINABLE CITIES AND SOCIETY

ISSN: 2210-6707

Year: 2018

Volume: 43

Page: 550-562

1 1 . 7 0 0

JCR@2022

JCR Journal Grade:1

Cited Count:

WoS CC Cited Count: 21

SCOPUS Cited Count: 31

ESI Highly Cited Papers on the List: 0 Unfold All

WanFang Cited Count:

Chinese Cited Count:

30 Days PV: 12

Online/Total:1237/10536882
Address:BJUT Library(100 Pingleyuan,Chaoyang District,Beijing 100124, China Post Code:100124) Contact Us:010-67392185
Copyright:BJUT Library Technical Support:Beijing Aegean Software Co., Ltd.