Abstract:
Determining the real energy consumption and usage pattern of a room air-conditioner (RAC) are important issues from the point of view of both RAC design and evaluation of its energy efficiency. An air conditioner's running time is fundamental data for the calculation of SEER and APF values. Therefore, in 2010, a nationwide investigation of RAC usage was conducted and 400 selected air-conditioning-units were monitored for a full year to obtain data on their cooling and heating usage. Two running time curves (cooling and heating) were obtained for the air-conditioners as a function of outdoor air temperatures using statistical analysis. The results show that the 27-30 degrees C temperature range accounts for more than 52% of the cooling time. Conversely, the 0-8 degrees C temperature range is associated with more than 75% of the heating time. The research presented in this paper has significantly contributed to China's new variable-speed RAC efficiency standard (GB21455-2013). It also has far-reaching implications for both the air-conditioner industry and energy policy in China due to its different method of calculating energy efficiency. (C) 2016 Elsevier Ltd. All rights reserved.