The heat pump system with scroll compressor flash-tank is presented, and it was compared with sub-cooler sys tem in structural characteristics. The experimental study and performance analyses of the heat pump prototype were implemented, and the results showed that the heating capacity of the prototype decreased along with lowering the evaporating temperature, but the decreasing rate is much slower than that of conventional air source heat pump system. The electric power input increased a little at the same time. The heat pump system with flash-tank can improve the heating performances more efficiently than the system with sub-cooler under low ambient temperature conditions, so it is much suitable to the small air source heat pump used in cold area.