Abstract:
Ventilation heat recovery is an important means of effectively reducing the energy consumption of buildings. The improve the performance of a heat pump heat recovery system under large temperature difference conditions winter, a triplex loop heat pump system, which contains three independent heat pump cycles, is proposed place of its single loop counterpart. Operating characteristics and system performance were analyzed while indoor temperature was constant at 20 degrees C and as outdoor temperature dropped from 15 degrees C to 20 degrees C. Result showed that with the decrease of the outdoor temperature, the mass flow rate and temperature effectiveness of the triplex loop heat recovery system decreased whereas the heating capacity and the coefficient of performanc (COP) increased. Under the experimental conditions, the COP of the triplex loop system had an advantage ove the traditional heat pump system when the outdoor temperature was below 2.5T. When the outdoor temperature was 20 degrees C, the COP of the triplex system could reach 9.33, which was 23.1% higher than that of th traditional system.