Abstract:
By conducting experimental measurements and numerical simulations of air distribution and microorganism pollutant distribution in the auditorium and game area in a gymnasium, pollutant dispersion control and indoor air quality improvement methods were put forward. The results show that the fungi and bacteria concentration levels are less than the magnitude of 10(3) CFU (colony-forming units) which meets the requirements of indoor air quality standard. The numerical simulation results quantitatively agree with the experimental data while some differences between theoretical data and experimental data exist in air distributions. People number in gymnasium plays an important role in affecting indoor air quality and the environmental parameters attained the standard.